LELab Sdn Bhd
18, Jalan Sungai Burung U32/U,
Seksyen 32, Bukit Rimau,
40460 Shah Alam,
Selangor Darul Ehsan, Malaysia.
+603-5525 3833
+603-5525 3832

Gas Detection

SBS-CH4 METHANE GAS DETECTOR

Methane Sensor and Monitoring System

Benefits

  • Protects life, property and company profits
  • Ideal for remote locations
  • Fail safe mode in event of loss of power
  • Up to three (3) sensors can be installed to main control to meet space coverage requirements

Features

  • Universal power inputs: 110/220 Vac and/or 12–48 Vdc input
  • Strobe light for visual alerts
  • Sensor status indicator LEDs on the main control
  • Modular design for optimal placement of sensor(s)

Installation

  • Wall or 2-gang junction box mountable
  • Mechanical relays are easily accessible:
    • Warning 25% relay, 15 A @ 120 Vac; 10 A @ 277 Vac; 10 A @ 28 Vdc
    • Alarm 50% relay, 0.5 A resistive @ 28 Vdc, 0.5 A @ 125 Vac
  • Redundant power supply capability; dual AC and/or DC power supply connections (DC power supply will operate as backup power source)
  • Indicator LEDs can be tested by pushing the red “TEST” button
  • Sensors can be tested in the field with the P/N CH4-TESTKIT

Detector can operate exhaust fans and building alarms / SCADA systems:

battery gas sensor diagram

Warning Settings: Should the concentration of methane gas in the air surrounding the sensor reach 25%LEL by volume, the “25%LEL Warning” yellow LED will light up on the main control of the unit. In addition, the 25%LEL internal relay will energize and can be used to activate an external exhaust fan.

Alarm Settings: Should the methane gas concentration reach 50%LEL by volume, the “50% Alarm” red LED will light up, the strobe will flash and an audible alarm will sound. In addition, the 50%LEL internal relay will energize and can be used to activate a building management/alarm system (via SCADA/Modbus).

SBS-CH4 Includes

  • Main unit
  • Methane sensor
  • 25 ft. cable

SBS-C4H10 BUTANE / ISOBUTANE GAS DETECTOR

Butane / Isobutane Sensor and Monitoring System

Benefits

  • Protects life, property and company profits
  • Ideal for remote locations
  • Fail safe mode in event of loss of power
  • Up to three (3) sensors can be installed to main control to meet space coverage requirements

Features

  • Universal power inputs: 110/220 Vac and/or 12–48 Vdc input
  • Strobe light for visual alerts
  • Sensor status indicator LEDs on the main control
  • Modular design for optimal placement of sensor(s)

Installation

  • Wall or 2-gang junction box mountable
  • Mechanical relays are easily accessible:
    • Warning 25% relay, 15 A @ 120 Vac; 10 A @ 277 Vac; 10 A @ 28 Vdc
    • Alarm 50% relay, 0.5 A resistive @ 28 Vdc, 0.5 A @ 125 Vac
  • Redundant power supply capability; dual AC and/or DC power supply connections (DC power supply will operate as backup power source)
  • Indicator LEDs can be tested by pushing the red “TEST” button
  • Sensors can be tested in the field with the P/N C4H10-TESTKIT

Detector can operate exhaust fans and building alarms / SCADA systems:

battery gas sensor diagram

Warning Settings: Should the concentration of butane / isobutane gas in the air surrounding the sensor reach 25%LEL by volume, the “25%LEL Warning” yellow LED will light up on the main control of the unit. In addition, the 25%LEL internal relay will energize and can be used to activate an external exhaust fan.


Alarm Settings: Should the butane / isobutane gas concentration reach 50%LEL by volume, the “50% Alarm” red LED will light up, the strobe will flash and an audible alarm will sound. In addition, the 50%LEL internal relay will energize and can be used to activate a building management/alarm system (via SCADA/Modbus).

SBS-C4H10 Includes

  • Main unit
  • Butane / Isobutane sensor
  • 25 ft. cable

SBS-C3H8 PROPANE GAS DETECTOR

Propane Sensor and Monitoring System


Benefits

  • Protects life, property and company profits
  • Ideal for remote locations
  • Fail safe mode in event of loss of power
  • Up to three (3) sensors can be installed to main control to meet space coverage requirements

Features

  • Universal power inputs: 110/220 Vac and/or 12–48 Vdc input
  • Strobe light for visual alerts
  • Sensor status indicator LEDs on the main control
  • Modular design for optimal placement of sensor(s)

Installation

  • Wall or 2-gang junction box mountable
  • Mechanical relays are easily accessible:
    • Warning 25% relay, 15 A @ 120 Vac; 10 A @ 277 Vac; 10 A @ 28 Vdc
    • Alarm 50% relay, 0.5 A resistive @ 28 Vdc, 0.5 A @ 125 Vac
  • Redundant power supply capability; dual AC and/or DC power supply connections (DC power supply will operate as backup power source)
  • Indicator LEDs can be tested by pushing the red “TEST” button
  • Sensors can be tested in the field with the P/N C3H8-TESTKIT

Detector can operate exhaust fans and building alarms / SCADA systems:

battery gas sensor diagram

Warning Settings: Should the concentration of propane gas in the air surrounding the sensor reach 25%LEL by volume, the “25%LEL Warning” yellow LED will light up on the main control of the unit. In addition, the 25%LEL internal relay will energize and can be used to activate an external exhaust fan.

Alarm Settings: Should the propane gas concentration reach 50%LEL by volume, the “50% Alarm” red LED will light up, the strobe will flash and an audible alarm will sound. In addition, the 50%LEL internal relay will energize and can be used to activate a building management/alarm system (via SCADA/Modbus).

SBS-C3H8 Includes

  • Main unit
  • Propane sensor
  • 25 ft. cable


SBS-H2-DoD HYDROGEN GAS DETECTOR

Hydrogen Sensor and Monitoring System


Benefits

  • Protects life, property and company profits
  • Ideal for remote locations
  • Fail safe mode in event of loss of power
  • Up to three (3) sensors can be installed to main control to meet space coverage requirements

Features

  • Universal power inputs: 110/220 Vac and/or 12–48 Vdc input
  • Strobe light for visual alerts
  • Sensor status indicator LEDs on the main control
  • Modular design for optimal placement of sensor(s)
  • NRTL/C Certified: UL Std. No 61010-1 & CAN/CSA-C22.2 No. 61010-1-12
  • UFC 3-520-05, January 2020

Installation

  • Wall or 2-gang junction box mountable
  • Mechanical relays are easily accessible:
    • Warning 0.5 % relay, 15 A @ 120 Vac; 10 A @ 277 Vac; 10 A @ 28 Vdc
    • Alarm 1% relay, 0.5 A resistive @ 28 Vdc, 0.5 A @ 125 Vac
  • Redundant power supply capability; dual AC and/or DC power supply connections (DC power supply will operate as backup power source)
  • Indicator LEDs can be tested by pushing the red “TEST” button
  • Sensors can be tested in the field with the P/N H2-TESTKIT

Detector can operate exhaust fans and building alarms / SCADA systems:

battery hydrogen sensor diagram

Warning Settings: Should the concentration of hydrogen gas in the air surrounding the sensor reach 0.5% by volume, the “0.5% Warning” yellow LED will light up on the main control of the unit. In addition, the 0.5% internal relay will energize and can be used to activate an external exhaust fan or a building management/alarm system (via SCADA Modbus).

Alarm Settings: Should the hydrogen gas concentration reach 1% by volume, the “1% Alarm” red LED will light up, the strobe will flash and an audible alarm will sound. In addition, the 1% internal relay will energize and can be used to activate a building management/alarm system (via SCADA/Modbus).

SBS-H2-DoD Includes

  • Main unit
  • Hydrogen sensor
  • 25 ft. cable

SBS-H2 HYDROGEN GAS DETECTOR

Hydrogen Sensor and Monitoring System

The SBS-H2 Hydrogen Detector is a hydrogen detection system with visual and audible alarms and 1% and 2% hydrogen relays.

The system comes complete with the main control, a highly accurate hydrogen gas sensor and a 25 ft. cable. This unit can be powered with AC and/or DC power and can be mounted directly to a wall or to an electrical box, making it extremely versatile and very user-friendly.

The SBS-H2 includes relays for remote connection to alarm/monitoring systems and for control of external relays for an exhaust fan.
 

Applications

  • Substations
  • Battery rooms
  • Uninterruptible power supply (UPS)
  • Battery cabinet systems
  • Battery charging areas
  • Hydrogen fueled back-up power systems

Benefits

  • Protects life, property and company profits
  • Ideal for remote locations
  • Fail safe mode in event of loss of power
  • Up to three (3) sensors can be installed to main control to meet space coverage requirements

Features

  • Universal power inputs: 110/220 Vac and/or 12–48 Vdc input
  • Strobe light for visual alerts
  • Sensor status indicator LEDs on the main control
  • Modular design for optimal placement of sensor(s)
  • NRTL/C Certified: UL Std. No 61010-1 & CAN/CSA-C22.2 No. 61010-1-12

Installation

  • Wall or 2-gang junction box mountable
  • Mechanical relays are easily accessible:
    • Warning 1 % relay, 15 A @ 120 Vac; 10 A @ 277 Vac; 10 A @ 28 Vdc
    • Alarm 2% relay, 0.5 A resistive @ 28 Vdc, 0.5 A @ 125 Vac
  • Redundant power supply capability; dual AC and/or DC power supply connections (DC power supply will operate as backup power source)
  • Indicator LEDs can be tested by pushing the red “TEST” button
  • Sensors can be tested in the field with the P/N H2-TESTKIT

SBS-H2 Includes

  • Main unit
  • Hydrogen sensor
  • 25 ft. cable

   

Switch to Mobile Version